Halogen Leak Detector



Halogen Leak Detector

The battery voltage display will remain as long as the BATTERY TEST key is depressed. Release the BATTERY TEST key to retun to normal operation. This function may be activated at any time during operation, and does not interfere alarm signals.

Automatic Circuit/Reset Feature

The Delicacy HLD200 feature an Automatic citcuit and a Reset function key that set the unit to ignore ambient consentrations of refrigerant.

● AUTOMATIC CIRCUIT-Upon initial power on, the unit automatically sets itself to ignore the level of refrigerant present at the tip. Only a level, or concentration, greater than this will cause an alarm. CAUTION :Be aware that this feature will the unit off, if you place the tip up to a known leak and switch the unit on, no leak will be indicated!

● RESET FEATURE-Pressing the RESET key during operation performs a similar function. When the RESET key is pressed it programs the ciruit to ignre the level of refrigerant present at the tip. This allows the user to ‘home-in’ on the souce of the leak (higher concentration). Similarly, the unit can be moved to fresh air and reset for maximum sensitivity. Resetting the unit with no refrigerant present (fresh air)causes any level above zero to be detected. Whenever the unit is reset the LED’ s(except the leftmost power indicator) Will turn red for 2 second. This provides a visual confirmation of the reset action.

Sensitivity Adjustment

The Delicacy HLD200 provides seven levels of sensitivity.the sensitivity level is indicated on the visual display when either the SENSITVITY↑ OR SENSITIVITY↓ keys are pressed. The base beeping tone is also an indication of sensitivity level.

OPERATING TIPS

All sustems-

Following any service to the refeigerant system and any other service which disturbs the refrigerant system.a leak test of the service ports of the retrigerant system should be done.

APPLICATIONS

The leak detector may also used to:

● Detect leaks in other systems and storage/recovery containers. It will respond to all halogenated (contains Chlorine of Fluorine) refrigerants. This includes, but is not limited to:

                CFCs e.g. R12, R11, R500, R503 etc…

                HCFCs e.g.R22, R123, R124, R502 etc…

      HFCs e.g.R134a, R404a, R125 etc…

                Blends such as AZ-50 HP62 MP39 etc

● Detect ethylene oxide gas leaks in hospital sterilizing equipment (it will detect the halogenated carrier gas)

● Detect SF-6 in high voltage circuit breakers

● Detect most gases that contain Chlorine, Fluorine, and Bromine (halogen gases)

● Detect cleaning agents used in dry cleaning applications such as perchloroethyl

● Two-year warranty

 

Power supply: 3V DC: two cell Alkaline batteries

Maximum sensitivity: Per Delicacy Rating Criteria Certified for R12,R22 and R134a @0.5 oz/yr.(14gr/yr)

Ultimate sensitivity: less than 0.1 oz/yr (3gr/yr) for all halogen based refrigerants

Sensing tip life: Approx. 30hours

Operating temperature: 30℉ to 125℉(0℃ to 52℃)

Battery life: Approximately 30 hours in normal use

Duty cycle: Continuous, no limitation

Response Time: Instaneous

Reset time: two second

Warm-up time: Approximately 6 seconds

Unit weight: 1,2lbs(560 grams)

Unit dimensions: 9”×2.5”×2.5” (22.9 ×6.5× 6.5cm)

Fixed probe length: 14”(35.5cm)